Key numbers from this manual
As printed in the manual, with metric and US units side by side. The typical range comes from all walk-in cooler manuals on this site that print the same figure.
| Clearance at the sides | 2” minimumbetween the drawn walk-in outline and existing building wall(s) | p. 17 |
|---|
Nor-Lake Walk-in Cooler questions
Answers taken from this manual. Each one links to the page it comes from.
How do I position the first wall panel?
- Match each panel’s part number on the floor plan with its interior label.
- Normally start with a corner panel.
- Place the end marked “Top” upward in the proper position.
- Set it on the floor or vinyl screed assembly in the designated location.
- If the walk-in has a floor, align the panel with the floor corner in both directions and lock it securely.
Manual: page 21
How do I seal the walk-in walls to the building floor?
- Apply NSF approved sealant along the bottom edges of all wall, corner, door, and partition panels.
- Cover both inner and outer perimeter-wall edges, plus both edges of partition walls.
- Make the seal continuous and airtight, including around shimming material.
- After the sealant sets, trim excess flush with the wall edges.
- Touch up any areas where the seal is imperfect.
Manual: page 27
Can I erect a floorless walk-in freezer on an ordinary existing floor?
No, a floorless walk-in freezer requires an existing floor specially prepared and adequately insulated for below freezing storage temperatures.
Manual: page 17
How do I shim a vinyl screed over minor low points?
- Use this method only for minor floor irregularities, not extremely irregular floors.
- Mark low points beside the drawn screed outline.
- Seal and secure the screed, then level around marked low points.
- Cut vinyl floor tile strips no wider than 5/8”.
- Place strips on the screed’s supporting shoulders.
- Tape the strips in place.
- Avoid shimming thicker than 3/4”.
Manual: page 16
Why is condensation forming around the walk-in door opening?
Occasional drops can occur during exceptionally high humidity; persistent moisture or freezing around the opening suggests heater-wire failure.
Manual: page 36
Can I leave the door-opening heater energized while refrigeration is off?
No. Extended operation without refrigeration can cause premature heater-wire failure.