Key numbers from this manual

As printed in the manual, with metric and US units side by side. The typical range comes from all commercial refrigerator manuals on this site that print the same figure.

Defrostautomaticdefrost cyclep. 22

Polar Commercial Refrigerator questions

Answers taken from this manual. Each one links to the page it comes from.

How do I program the freezer’s electric defrost timer?

Program it by positioning the timer’s trippers for operating and defrost periods.

  1. Treat each tripper as 15 minutes of defrost time.
  2. Place trippers on the inner ring during periods requiring refrigeration, selecting ON.
  3. Move trippers to the outside wherever DEFROST should occur.
  4. Schedule defrost during low-activity periods; two to four cycles daily are typical.

Manual: page 21

What happens during a freezer defrost cycle?

The compressor and evaporator fans stop while heaters warm the coil, melting frost and ice. The walk-in temperature rises above its set point during the 30-minute cycle, then returns afterward.

Manual: page 21

What does ASd mean on the control?

ASd sets the minimum off-time before the output relay can restart, even when cooling is requested.

Manual: page 12

What temperature scales can this control use?

Fahrenheit (°F) or Celsius (°C).

Manual: page 12

How do I move through the A421 control’s setup menus?
  1. Use the Basic menu or Advanced setup menu for parameter setup.
  2. At a parameter screen, press Down or Up to browse parameter codes.
  3. Press Down or Up to browse the available values for that parameter.
  4. Press Down and Up together to return to the Main screen.

Manual: page 14

How do I manually start or stop a defrost cycle?
  1. Set Defrost Interval (dI) to 0.
  2. Set dFt between 1 minute and 99 minutes.
  3. During normal On/Off operation, set SdF to 1 to start.
  4. During a defrost cycle, set SdF to 0 to stop it.

Manual: page 16

How do I change a parameter in the Advanced menu?
  1. From the Main screen, hold Down and Up together for 5 seconds.
  2. Use Down or Up to reach the desired parameter code.
  3. Press MENU to view that parameter’s current value.
  4. Use Down or Up to select an available value.
  5. Press MENU to save the selection and move to the next parameter code.

Manual: page 16

Similar Polar commercial refrigeration

Polar GL180User Manual56 pages
Polar DA462User Manual48 pages
Polar GL001Instruction Manual48 pages
Polar DA546Instruction Manual48 pages
Polar CS102User Manual48 pages
Polar CG841Instruction Manual48 pages
Polar CB507Instruction Manual48 pages
Polar GM498Instruction Manual40 pages
All Polar commercial refrigeration →