Key numbers from this manual

As printed in the manual, with metric and US units side by side. The typical range comes from all commercial refrigerator manuals on this site that print the same figure.

Fridge factory setting38.0FAll models, factory settingTypical for commercial refrigeration: 35 to 38 °F (2 to 3 °C)p. 6
Fridge adjustment range35.5 and 40.5 degrees F.All modelsTypical for commercial refrigeration: 34 to 45 °F (1 to 7 °C)p. 6
Wait before use3 hoursIf the unit was tipped onto its backp. 8
Clearance above0" (0 cm)Minimum top clearanceTypical for commercial refrigeration: 0 to 12 in (0 to 30.5 cm)p. 7
Clearance at the sides0" (0 cm)Minimum left and right clearanceTypical for commercial refrigeration: 0 to 4 in (0 to 10.2 cm)p. 7
Clearance behind2" (5.1 cm)Minimum rear clearanceTypical for commercial refrigeration: 1 to 4 in (2.5 to 10.2 cm)p. 7
DefrostautomaticDanfoss controllermanualElectronic Controllerp. 11 p. 13

Beverage-Air UCR*41AHC********* questions

Answers taken from this manual. Each one links to the page it comes from.

What minimum clearances does the refrigerator need?

The specified minimums are 0" above, 0" at the sides, 2" behind, and 3" below.

LocationMinimum clearance
Top0"
Left and right sides0"
Rear2"
Below3"

Manual: page 7

How do I clean the refrigerator door gasket?

Disconnect power before cleaning the gasket.

  1. Remove food and store it at a safe temperature.
  2. Unplug the unit or switch off its breaker.
  3. Scrub the gasket with warm 100 °F to 110 °F detergent solution and a soft brush.
  4. Rinse with clean water and let the gasket air dry.
  5. Restore power, then return food after the unit reaches a safe temperature.

Manual: page 20

How do I defrost the refrigerator?

Use the procedure for your controller:

  • Danfoss controller: Push and immediately release the melting or defrost button.
  • Electronic Controller: Quick-press and release DEFROST (ESC) to activate manual defrost.

Manual: page 11, page 13

How do I restore power when the refrigerator is silent and not cooling?
  • No power connection. Connect the refrigerator to a proper voltage circuit.
  • Tripped fuse or breaker. Replace the fuse or restore the circuit breaker.
  • Loose outlet plug. Check the outlet connection and replace it if needed.

Manual: page 24

What does the Alarm LED indicate?

It indicates the current alarm state:

LED stateMeaning
On fixedALARM Present
FlashingALARM Silenced
OffNo Alarm

Manual: page 13

Why is the Compressor LED flashing?

A flashing Compressor LED indicates a delay, protection, or blocked activation.

Manual: page 13

Beverage-Air UCR*41AHC********* compared with other brands

Commercial Refrigeration from other brands with the most of the same figures in their manuals. Values as printed in each manual.

Beverage-Air UCR*41AHC*********Other Commercial RefrigeratorSummit AL57GGram Commercial Refrigerator
Fridge factory setting38.0F34 °F to 38 °F (1 °C, 3 °C)38 °F, or 3 °C5 °C (41 °F)
Fridge adjustment range35.5 and 40.5 degrees F34 °F to 38 °F (1 °C, 3 °C)36 °F to 43 °F (2 °C, 6 °C)2 to 12 °C (36 to 54 °F)
Wait before use3 hoursat least 24 hoursat least 2 hoursat least 2 hours
Clearance above0" (0 cm)12" (30.5 cm)2 to 3 mm (about 1/10")250 mm (9.8 in)
Clearance at the sides0" (0 cm)2" (5.1 cm)5 inches (127mm) (12.7 cm)20 mm (0.8 in)
Clearance behind2" (5.1 cm)2" (5.1 cm)5 inches (127mm) (12.7 cm)max. 75 mm (3 in)

Similar Beverage-Air commercial refrigeration

Beverage-Air UCRFModel family UCROperating Instructions34 pages
Beverage-Air UCF*36AHC*********Installation & Operation Manual25 pages
Beverage-Air BF200RB-PFO-XLOperating Instructions74 pages
Beverage-Air MT08-1[#]User Manual69 pages
Beverage-Air PR3HC-1A*S******Installation & Operation Manual54 pages
Beverage-Air BB58HC****G*******Installation & Operation Manual46 pages
Beverage-Air DD58HC****G*******Installation & Operation Manual39 pages
Beverage-Air 3071629RV05Operating Instructions39 pages
All Beverage-Air commercial refrigeration →