Key numbers from this manual
As printed in the manual, with metric and US units side by side. The typical range comes from all commercial refrigerator manuals on this site that print the same figure.
| Fridge factory setting | 33 °F cut-in, 29 °F cut-out (1 °C, -2 °C) colder than mostPans, factory settingTypical for commercial refrigeration: 35 to 38 °F (2 to 3 °C) | p. 20 |
|---|
Hill Phoenix Commercial Refrigerator questions
Answers taken from this manual. Each one links to the page it comes from.
What are the factory cut-in and cut-out temperature settings?
Factory settings are listed below, but store conditions may require controller adjustments.
| Case area | Cut-in (°F) | Cut-out (°F) |
|---|---|---|
| Pans | 33 °F | 29 °F |
| Top Coil | 36 °F | 31 °F |
Manual: page 20
Why is the case losing proper temperature?
- Overloaded display. Keep products within the designated air curtain; do not cover discharge and return air sections.
- Store conditions. Adjust the controls because factory settings may need changes for local operating conditions.
Manual: page 20
What does a dash mean in the defrost table?
A dash marks information that does not apply.
Manual: page 7
Why does the display show dA?
The dA message means the door input stayed active beyond the did delay with i1F = dor; disable the input to stop the alarm.
Manual: page 35
What does the CA alarm mean?
It identifies one of these configured alarm conditions:
- Serious alarm. With i1F = bAL, CA appears after did; relay outputs switch off until input deactivation.
- Pressure alarm. With i1F = PAL, CA appears after nPS activations during did; switch the instrument off and on.
Manual: page 35
What should I do when Err appears during Hot Key programming?
- For failed upload, remove the Hot key to abort the operation.
- For failed download, turn the instrument off and on to restart, or remove the Hot key to abort.
Manual: page 35
Error codes in this manual
| Code | Meaning | What to do | |
|---|---|---|---|
| CA | Serious external alarm is active. | Disable the digital input to stop the alarm. | p. 35 |
| dA | Door remains open. | Close the door or disable the digital input. | p. 35 |
| EA | External alarm is active. | Disable the digital input to stop the alarm. | p. 35 |
| Err | Hot Key programming failed. | Retry programming, or remove the Hot Key to cancel. | p. 35 |
| HA | Maximum temperature alarm. | The alarm stops automatically when temperature returns to normal. | p. 35 |
| HA2 | Condenser high temperature alarm. | The alarm stops automatically when temperature returns to normal. | p. 35 |
| LA | Minimum temperature alarm. | The alarm stops automatically when temperature returns to normal. | p. 35 |
| LA2 | Condenser low temperature alarm. | The alarm stops automatically when temperature returns to normal. | p. 35 |
| P1 | Room thermostat probe failure. | Check probe connections before replacing the probe. | p. 35 |
| P2 | Evaporator probe failure. | Check probe connections before replacing the probe. | p. 35 |
| P3 | Third probe failure. | Check probe connections before replacing the probe. | p. 35 |
| P4 | Fourth probe failure. | Check probe connections before replacing the probe. | p. 35 |
Similar Hill Phoenix commercial refrigeration
| Hill Phoenix Commercial Refrigeration Installation & Operation Manual | Installation & Operation Manual | 54 pages |
|---|---|---|
| Hill Phoenix Commercial Refrigeration Installation & Operation Manual | Installation & Operation Manual | 52 pages |
| Hill Phoenix Commercial Refrigeration Installation & Operation Manual | Installation & Operation Manual | 44 pages |
| Hill Phoenix Commercial Refrigeration Installation & Operation Manual | Installation & Operation Manual | 44 pages |
| Hill Phoenix Commercial Refrigeration Installation & Operation Manual | Installation & Operation Manual | 36 pages |
| Hill Phoenix P056170D | Installation & Operation Manual | 36 pages |
| Hill Phoenix PF-54-SC | Installation & Operation Manual | 33 pages |
| Hill Phoenix Commercial Refrigeration Installation & Operation Manual | Installation & Operation Manual | 32 pages |