Key numbers from this manual

As printed in the manual, with metric and US units side by side. The typical range comes from all commercial refrigerator manuals on this site that print the same figure.

Fridge factory setting33 °F cut-in, 29 °F cut-out (1 °C, -2 °C) colder than mostPans, factory settingTypical for commercial refrigeration: 35 to 38 °F (2 to 3 °C)p. 20

Hill Phoenix Commercial Refrigerator questions

Answers taken from this manual. Each one links to the page it comes from.

What are the factory cut-in and cut-out temperature settings?

Factory settings are listed below, but store conditions may require controller adjustments.

Case areaCut-in (°F)Cut-out (°F)
Pans33 °F29 °F
Top Coil36 °F31 °F

Manual: page 20

Why is the case losing proper temperature?
  • Overloaded display. Keep products within the designated air curtain; do not cover discharge and return air sections.
  • Store conditions. Adjust the controls because factory settings may need changes for local operating conditions.

Manual: page 20

What does a dash mean in the defrost table?

A dash marks information that does not apply.

Manual: page 7

Why does the display show dA?

The dA message means the door input stayed active beyond the did delay with i1F = dor; disable the input to stop the alarm.

Manual: page 35

What does the CA alarm mean?

It identifies one of these configured alarm conditions:

  • Serious alarm. With i1F = bAL, CA appears after did; relay outputs switch off until input deactivation.
  • Pressure alarm. With i1F = PAL, CA appears after nPS activations during did; switch the instrument off and on.

Manual: page 35

What should I do when Err appears during Hot Key programming?
  • For failed upload, remove the Hot key to abort the operation.
  • For failed download, turn the instrument off and on to restart, or remove the Hot key to abort.

Manual: page 35

Error codes in this manual

CodeMeaningWhat to do
CASerious external alarm is active.Disable the digital input to stop the alarm.p. 35
dADoor remains open.Close the door or disable the digital input.p. 35
EAExternal alarm is active.Disable the digital input to stop the alarm.p. 35
ErrHot Key programming failed.Retry programming, or remove the Hot Key to cancel.p. 35
HAMaximum temperature alarm.The alarm stops automatically when temperature returns to normal.p. 35
HA2Condenser high temperature alarm.The alarm stops automatically when temperature returns to normal.p. 35
LAMinimum temperature alarm.The alarm stops automatically when temperature returns to normal.p. 35
LA2Condenser low temperature alarm.The alarm stops automatically when temperature returns to normal.p. 35
P1Room thermostat probe failure.Check probe connections before replacing the probe.p. 35
P2Evaporator probe failure.Check probe connections before replacing the probe.p. 35
P3Third probe failure.Check probe connections before replacing the probe.p. 35
P4Fourth probe failure.Check probe connections before replacing the probe.p. 35
All Hill Phoenix error codes →

Similar Hill Phoenix commercial refrigeration

Hill Phoenix Commercial Refrigeration Installation & Operation ManualInstallation & Operation Manual54 pages
Hill Phoenix Commercial Refrigeration Installation & Operation ManualInstallation & Operation Manual52 pages
Hill Phoenix Commercial Refrigeration Installation & Operation ManualInstallation & Operation Manual44 pages
Hill Phoenix Commercial Refrigeration Installation & Operation ManualInstallation & Operation Manual44 pages
Hill Phoenix Commercial Refrigeration Installation & Operation ManualInstallation & Operation Manual36 pages
Hill Phoenix P056170DInstallation & Operation Manual36 pages
Hill Phoenix PF-54-SCInstallation & Operation Manual33 pages