Key numbers from this manual

As printed in the manual, with metric and US units side by side. The typical range comes from all commercial refrigerator manuals on this site that print the same figure.

Fridge factory setting36 FFactory settingTypical for commercial refrigeration: 35 to 38 °F (2 to 3 °C)p. 12
Wait before use24 hoursif the unit is tipped onto its backp. 8
Clearance above14 in. (35.6 cm) needs more space than mostabove the unitTypical for commercial refrigeration: 0 to 12 in (0 to 30.5 cm)p. 7
Clearance at the sides0.0 in. (0 cm)left side and right sideTypical for commercial refrigeration: 0 to 4 in (0 to 10.2 cm)p. 7
Defrostautomatically defrost as neededp. 12

Victory ACRS questions

Answers taken from this manual. Each one links to the page it comes from.

Why does the refrigerator run constantly even though it cools?
  • Dirty condenser. Clean the condenser.
  • Iced evaporator. Defrost the evaporator.
  • High room temperature. Reduce the room temperature.
  • Temperature control problem. Adjust or replace the control.

Manual: page 23

The refrigerator is not cooling and silent. What should I check?
  • Unit unplugged. Connect it to the proper voltage circuit.
  • Tripped fuse or circuit breaker. Replace the fuse or reset the breaker.
  • Loose power cord plug. Check the outlet connection and replace it as needed.

Manual: page 23

How often should I clean the door gasket?

Weekly, during the unit’s interior cleaning routine.

Manual: page 20

What does OPd mean?

OPd identifies the Door open alarm; the alarm is listed as inactive with automatic reset.

Manual: page 19

How do I start a manual defrost?

Push and immediately release the melting or defrost button to begin a manual defrost.

Manual: page 12

Why does the refrigerator defrost at different times?

The refrigerator defrosts automatically as needed, so it has no scheduled defrost time.

Manual: page 12

Why is the unit silent and not cooling?
  • The unit is unplugged. Connect it to the proper voltage circuit.
  • The fuse or circuit breaker has tripped. Replace the fuse or reset the breaker.
  • The power plug is loose. Check the outlet connection and replace it as needed.

Manual: page 23

How do I restore power after cleaning the cabinet interior?
  1. Remove food and shelves, then store the food at a safe temperature.
  2. Disconnect power by unplugging the unit or switching off the breaker.
  3. Clean the interior with warm 100oF to 110oF detergent solution and a soft brush.
  4. Rinse surfaces with clean water and let them air dry.
  5. Return and secure the shelves, then restore power.
  6. Return food after the unit reaches a safe temperature.

Manual: page 20

Error codes in this manual

CodeMeaningWhat to do
Ad2Defrost ended because of timeoutReset occurs automatically.p. 19
AH1High temperature alarm 1Reset occurs automatically.p. 19
AH2High temperature alarm 2Reset occurs automatically.p. 19
AL1Low temperature alarm 1Reset occurs automatically.p. 19
AL2Low temperature alarm 2Reset occurs automatically.p. 19
E1Probe Pb1 failureReset occurs automatically.p. 19
E2Probe Pb2 failureReset occurs automatically.p. 19
E3Probe Pb3 failureReset occurs automatically.p. 19
E4Probe Pb4 failureReset occurs automatically.p. 19
E5Probe Pb5 failureReset occurs automatically.p. 19
E10Clock alarmReset occurs automatically.p. 19
EAExternal alarmReset occurs automatically.p. 19
EiVirtual probe failureReset occurs automatically.p. 19
ELLINK2 probe failureReset occurs automatically.p. 19
HiPHigh voltage alarmReset occurs automatically.p. 19
HPALow pressure switch alarmReset occurs automatically.p. 19
LoPLow voltage alarmReset occurs automatically.p. 19
LPAHigh pressure switch alarmReset occurs automatically.p. 19
nPAGeneral pressure switch alarmReset occurs automatically.p. 19
OPdDoor open alarmReset occurs automatically.p. 19
PAGeneral pressure switch alarmReset manually.p. 19
PrrPreheating alarmReset occurs automatically.p. 19
All Victory error codes →

Victory ACRS compared with other brands

Commercial Refrigeration from other brands with the most of the same figures in their manuals. Values as printed in each manual.

Victory ACRSOther Commercial RefrigeratorSummit FF64BCSSGram Commercial Refrigerator
Fridge factory setting36 F34 °F to 38 °F (1 °C, 3 °C)38 °F, or 3 °C5 °C (41 °F)
Wait before use24 hoursat least 24 hoursabout 2 hoursat least 2 hours
Clearance above14 in12" (30.5 cm)4” (102mm)250 mm (9.8 in)
Clearance at the sides0.0 in2" (5.1 cm)5” (127mm)20 mm (0.8 in)

Similar Victory commercial refrigeration

Victory VERSA-1D-GD-HCInstallation & Operation Manual53 pages
Victory VEFSA-1D-HD-HC-*Installation & Operation Manual48 pages
Victory VBCFT-20-202PU-HCOperating Instructions42 pages
Victory Commercial Refrigeration Operating InstructionsOperating Instructions38 pages
Victory RS-2D-S1-EW-HCInstallation & Operation Manual34 pages
Victory RIS-2D-S1-HCInstallation & Operation Manual32 pages
Victory Commercial Refrigeration Operating InstructionsOperating Instructions31 pages
Victory VWR36HC*********Installation & Operation Manual31 pages
All Victory commercial refrigeration →