Key numbers from this manual

As printed in the manual, with metric and US units side by side. The typical range comes from all commercial refrigerator manuals on this site that print the same figure.

Fridge factory setting36 °F (2 °C)refrigeratorsTypical for commercial refrigeration: 35 to 38 °F (2 to 3 °C)p. 20
Fridge adjustment range36 °F and 50 °F (2 °C and 10 °C)refrigeratorsTypical for commercial refrigeration: 34 to 45 °F (1 to 7 °C)p. 20
Freezer factory setting-3 °F (-19 °C)freezersTypical for commercial refrigeration: -4 to 0 °F (-20 to -18 °C)p. 20
Freezer adjustment range-10 °F and 25 °F (-23 °C and -4 °C)freezersTypical for commercial refrigeration: -8 to 3 °F (-22 to -16 °C)p. 20
Door-open alarm after3 minutesBoth display and beeps alarm when the door remains open longer than 3 minutesTypical for commercial refrigeration: 1 to 5 minutesp. 25
Clearance above10" (25 cm)minimum overhead clearance for proper ventilationTypical for commercial refrigeration: 0 to 12 in (0 to 30.5 cm)p. 16
Clearance at the sides4" (11 cm)minimum clearance from side walls for proper ventilationTypical for commercial refrigeration: 0 to 4 in (0 to 10.2 cm)p. 16
Defrostoff-cycle, temperature-initiated or time-initiatedrefrigeratorstime-initiated, heatedfreezersp. 21
Room temperature range45 °F to 100 °F (7 °C to 38 °C)ambient temperature range throughout the yearTypical for commercial refrigeration: 60 to 100 °F (16 to 38 °C)p. 16

Hoshizaki Commercial Refrigerator questions

Answers taken from this manual. Each one links to the page it comes from.

What installation clearance does the appliance need?

Provide these minimum clearances for proper ventilation.

LocationMinimum clearance
Side walls4" (11 cm)
Overhead10" (25 cm)

Other brands: Other 12" (30.5 cm) · Summit 4“(102mm) · True 1" (25.4 mm) Compare all

Manual: page 16

What room temperature range is allowed?

45 °F to 100 °F (7 °C to 38 °C) is allowed year-round.

Other brands: Other not higher than 38℃ · Summit above 44 °F (7 °C) and below 90 °F (32 °C) · True 60 °F (15.5 °C) to 104 °F (40 °C) Compare all

Manual: page 16

Why is the door alarm sounding?

The door has remained open longer than 3 minutes. Close it, then press RESET to silence the alarm for 3 minutes.

Other brands: Other 2 minutes · Summit 60 seconds · True five (5) Compare all

Manual: page 25

How do I clean the door gasket?

Wash the door gasket often using mild soap and warm water; this removes dirt and grease.

Manual: page 26

What happens during refrigerator or freezer defrosting?

Refrigerators use several defrost methods, while freezers use timed heated defrosting.

ApplianceDefrost methodDisplay during defrost
RefrigeratorOff-cycle, temperature or time initiatedCabinet temperature
FreezerTimed, heateddEF

Manual: page 21

How do I change the timed defrost frequency?

Contact your local Hoshizaki distributor or Technical Support before changing the frequency.

  1. Hold up and down simultaneously for 3 seconds; press ENTER until dF appears.
  2. For refrigerators, choose 0 to 12 defrosts per 24 hours.
  3. For freezers, choose 1 to 12 defrosts per 24 hours.
  4. Press up or down until the desired frequency displays.
  5. Press ENTER repeatedly to save; 15 seconds without input leaves the setting unchanged.
  6. Without power cycling, timing changes after the next defrost under the previous interval.
  7. To apply the new interval immediately, turn the appliance off and back on.

Manual: page 21, page 22

How do I apply a changed time-initiated defrost setting immediately?

Save the new setting, then restart the appliance so the revised timing begins immediately.

  1. Press ENTER repeatedly until the appliance returns to normal display mode.
  2. Turn the appliance off and back on.

Manual: page 22

Why does the compressor wait before restarting?

The compressor has a 2 1/2 minute minimum off-time and on-time, with possible variation from overload or high-pressure activation.

Manual: page 23

Error codes in this manual

CodeMeaningWhat to do
CFCondenser temperature is outside the normal operating range.Clean the air filter or condenser, allow the sensor to reset, then press RESET.p. 25
doorThe door is open, possibly longer than three minutes.Close the door. Press RESET to silence the alarm for three minutes.p. 25
E3Defrost lasted longer than one hour, and the control board ended defrost.Press RESET. If four consecutive defrosts exceed one hour, call a qualified service technician.p. 24
E4Compressor discharge pressure is outside the normal operating range.Clean the air filter or condenser, press RESET, and call service if frequent.p. 24
E6Line voltage has been too high for at least ten seconds.Press RESET for five minutes. If frequent, call a qualified service technician.p. 24
E7Line voltage has been too low for at least ten seconds.Press RESET for five minutes. If frequent, call a qualified service technician.p. 24
All Hoshizaki error codes →

Hoshizaki Commercial Refrigerator compared with other brands

Commercial Refrigeration from other brands with the most of the same figures in their manuals. Values as printed in each manual.

Hoshizaki Commercial RefrigeratorGram Commercial RefrigeratorOther Commercial RefrigeratorSummit FF64BCSS
Fridge factory setting36 °F (2 °C)5 °C (41 °F)34 °F to 38 °F (1 °C, 3 °C)38 °F/3 °C
Fridge adjustment range36 °F and 50 °F (2 °C and 10 °C)2 to 12 °C (36 to 54 °F)34 °F to 38 °F (1 °C, 3 °C)36 °F/2 °C to 43 °F/6 °C
Freezer factory setting-3 °F (-19 °C)-18 °C (0 °F)-7°Fto -1 °F (-22 °C, -18 °C)0 °F/-18 °C
Freezer adjustment range-10 °F and 25 °F (-23 °C and -4 °C)-10 to -22 °C (14 to -8 °F)-7°Fto -1 °F (-22 °C, -18 °C)-11 °F/-24 °C to 11 °F/-12 °C
Door-open alarm after3 minutesmore than 2 minutes··
Clearance above10" (25 cm)250 mm (9.8 in)12" (30.5 cm)4“(102mm)
Clearance at the sides4" (11 cm)20 mm (0.8 in)2" (5.1 cm)5” (127mm)