True error codes

69 True error and alarm codes from 11 manuals: what each code means and what the manual says to do.

69 codes11 manuals

Codes and what they mean

As described in each manual. The same code can mean different things on different models, so check the model column.

CodeMeaningWhat to doManual
COMDisplay is not communicating with the control board.Check display and board connections; the unit may need a firmware update.TCIM-422-FA1-A~*-#
COMMDisplay communication error.TCIM-422-FA1-A~*-#
dADoor switch alarm.TRM2L******#*******#, Commercial Refrigerator
dEFDefrost is in progress.TRM2L******#*******#, Commercial Refrigerator, TGO-27-POP01, TGO-27-POP01
dEFDefrost is activeGDM-23-HST02-HC
dEFDefrost is currently running.GDM-49-SCI-HC
dLcDoor lock or unlock password entryTGO-27-POP01, GDM-23-HST02-HC, TGO-27-POP01, GDM-23-HST02-HC
doDoor open alarmTGO-27-POP01, GDM-23-HST02-HC, TGO-27-POP01, GDM-23-HST02-HC
doThe cabinet door is open.GDM-49-SCI-HC
doDoor openOpen for ≥ 60 secCommercial Refrigerator
E1Probe t1 failureTGO-27-POP01
E1Probe 1 has failedGDM-23-HST02-HC
E1Temperature probe 1 has failed.GDM-49-SCI-HC
E1Probe 1 failureTGO-27-POP01
E1Probe t1 has failedGDM-23-HST02-HC, GDM-49-SCI-HC
E1Evaporator outlet temperature probe error.TCIM-422-FA1-A~*-#
E1T1 probe is open or shorted.Replace the probe.TCIM-422-FA1-A~*-#
E2Probe t2 failureTGO-27-POP01
E2Probe 2 has failedGDM-23-HST02-HC
E2Temperature probe 2 has failed.GDM-49-SCI-HC
E2Probe 2 failureTGO-27-POP01
E2Probe t2 has failedGDM-23-HST02-HC, GDM-49-SCI-HC
E2Ambient air temperature probe error.TCIM-422-FA1-A~*-#
E2T2 probe is open or shorted.Replace the probe.TCIM-422-FA1-A~*-#
E3Probe t3 failureTGO-27-POP01
E3Probe 3 has failedGDM-23-HST02-HC
E3Temperature probe 3 has failed.GDM-49-SCI-HC
E3Probe 3 failureTGO-27-POP01
E3Probe t3 has failedGDM-23-HST02-HC, GDM-49-SCI-HC
E3Sump water temperature probe error.TCIM-422-FA1-A~*-#
E3T3 probe is open or shorted.Replace the probe.TCIM-422-FA1-A~*-#
E4Supply water temperature probe error.TCIM-422-FA1-A~*-#
E4T4 probe is open or shorted.Replace the probe.TCIM-422-FA1-A~*-#
E6High pressure safety switch is open.TCIM-422-FA1-A~*-#
E6Discharge pressure exceeded 370 psi.Clean the air filter and condenser coil; verify the condenser fan operates.TCIM-422-FA1-A~*-#
E7High pressure transducer error.TCIM-422-FA1-A~*-#
E7HP1 transducer signal is lost or indicates high pressure.Check transducer wiring to the board; replace the transducer.TCIM-422-FA1-A~*-#
E8Low pressure transducer error.TCIM-422-FA1-A~*-#
E8LP1 transducer signal is lost or indicates low pressure.Check transducer wiring to the board; replace the transducer.TCIM-422-FA1-A~*-#
E9Water level sensor input error.TCIM-422-FA1-A~*-#
E9Water level sensor signal is lost.Check sensor tubing and verify the board pressure chip has good contact.TCIM-422-FA1-A~*-#
E10Ice level sensor communication error.TCIM-422-FA1-A~*-#
E11Evaporator outlet temperature is too low during freezing.TCIM-422-FA1-A~*-#
E11T1 fell below minus 10 degrees during the first two freeze minutes.Check probe resistance and location, pump operation, and whether the previous ice sheet fell.TCIM-422-FA1-A~*-#
E12Evaporator outlet temperature is too high.TCIM-422-FA1-A~*-#
E12Evaporator outlet temperature exceeded 113 degrees Fahrenheit.Verify cold water supply and ambient temperatures; test the probe.TCIM-422-FA1-A~*-#
E13Evaporator outlet temperature is too low.TCIM-422-FA1-A~*-#
E13Evaporator outlet temperature fell below minus 20 degrees Fahrenheit.Test the probe, outlet temperature, pump operation, and water supply.TCIM-422-FA1-A~*-#
E14Ambient air temperature is too high.TCIM-422-FA1-A~*-#
E14Ambient temperature exceeded 130 degrees Fahrenheit.Verify ambient temperature, test the probe, and verify condenser motor operation.TCIM-422-FA1-A~*-#
E15Ambient air temperature is too low.TCIM-422-FA1-A~*-#
E15Ambient temperature fell below 33 degrees Fahrenheit.Verify ambient temperature and test the probe.TCIM-422-FA1-A~*-#
E16Sump water temperature is too high.TCIM-422-FA1-A~*-#
E16Water trough temperature exceeded 113 degrees Fahrenheit.Verify trough water temperature and test the probe.TCIM-422-FA1-A~*-#
E17Sump water temperature is too low.TCIM-422-FA1-A~*-#
E17Water trough temperature fell below 25 degrees Fahrenheit.Verify trough water temperature and test the probe.TCIM-422-FA1-A~*-#
E18Supply water temperature is too high.TCIM-422-FA1-A~*-#
E18Incoming water temperature exceeded 124 degrees Fahrenheit.Check water supply temperature and test the probe.TCIM-422-FA1-A~*-#
E19Supply water temperature is too low.TCIM-422-FA1-A~*-#
E19Incoming water temperature fell below 33 degrees Fahrenheit.Check water supply temperature and test the probe.TCIM-422-FA1-A~*-#
E20High pressure detected at the high pressure transducer.TCIM-422-FA1-A~*-#
E20HP1 head pressure exceeded 320 to 360 psi, depending on model.Clean the air filter and condenser coil; verify proper condenser fan operation.TCIM-422-FA1-A~*-#
E21Drain switch alarm.TCIM-422-FA1-A~*-#
E22Freeze cycle takes too long.TCIM-422-FA1-A~*-#
E22Freeze cycle exceeded 40 minutes.Verify compressor operation and check high and low side pressures.TCIM-422-FA1-A~*-#
E23Calculation produced a negative value.TCIM-422-FA1-A~*-#
E23Sump water level fell below the freeze cycle differential.Check for leaks near the evaporator cover, harvest flap, and drain valve.TCIM-422-FA1-A~*-#
E24Fill cycle takes too long.TCIM-422-FA1-A~*-#
E24Sump tank did not fill within 30 minutes.Verify water supply; check the incoming filter and inlet valve.TCIM-422-FA1-A~*-#
E25Purge cycle takes too long.TCIM-422-FA1-A~*-#
E25Sump water did not drain to the proper level within four minutes.Check drain valve voltage, clear and vent the drain, and check the sump drain.TCIM-422-FA1-A~*-#
E26Harvest cycle takes too long.TCIM-422-FA1-A~*-#
E26Bin switch failed to open during three harvests, or startup temperature stayed too low.Check stuck switch contacts, evaporator freezing, and ice sheet pattern.TCIM-422-FA1-A~*-#
E27Water leakage detected.TCIM-422-FA1-A~*-#
E27Water level fell below the harvest initiation level during the first five minutes.Check excessive splashing, the water curtain, harvest flap, and leaking drain valve.TCIM-422-FA1-A~*-#
E28Pump motor alarm.TCIM-422-FA1-A~*-#
E28During startup, water level did not fall below 43 millimeters within 60 seconds.Check pump voltage and verify the inlet valve shuts off.TCIM-422-FA1-A~*-#
E29Sump tank did not fill within three minutes.Check the water filter, incoming pressure, inlet valve, and drain valve.TCIM-422-FA1-A~*-#
E30Biozone communication or bulb problem.Check communication or replace the bulb.TCIM-422-FA1-A~*-#
E30UV Biozone system failure.Check the UV menu for low current, high current, or exceeded lamp time.TCIM-422-FA1-A~*-#
E31Hot gas valve alarm.TCIM-422-FA1-A~*-#
E31High side pressure exceeded 165 psi during harvest.Follow the No Harvest or Frozen In flow chart.TCIM-422-FA1-A~*-#
E32Low suction pressure.TCIM-422-FA1-A~*-#
E32Low side pressure fell below 10 psi during freezing.Check cycle times, pressures, ice pattern, leaks, and restrictions.TCIM-422-FA1-A~*-#
E33Secondary high side transducer failed.Check transducer wiring to the control board; replace the transducer.TCIM-422-FA1-A~*-#
E34Secondary low side transducer failed.Check transducer wiring to the control board; replace the transducer.TCIM-422-FA1-A~*-#
EdtEnd time for timed actionsTGO-27-POP01, TGO-27-POP01, GDM-23-HST02-HC
EdtEnd time for scheduled actionsGDM-23-HST02-HC
EEData or memory failure.TRM2L******#*******#, Commercial Refrigerator
H2OWater fill is slow.Check the water connection.TCIM-422-FA1-A~*-#
HAMaximum cabinet temperature alarm.TRM2L******#*******#
HAMaximum temperature alarmCommercial Refrigerator
HA2Maximum condenser liquid line temperature alarm.TRM2L******#*******#
hiAppliance high temperature alarmTGO-27-POP01, GDM-23-HST02-HC, TGO-27-POP01, GDM-23-HST02-HC
hiThe cabinet temperature is too high.GDM-49-SCI-HC
hiHigh temperature≥ 46 °F (8 °C) for ≥ 5 minCommercial Refrigerator
hiCabinet high temperature alarm.GDM-49-SCI-HC
hLA/LocHealth Safety Alarm or lockout is activeTGO-27-POP01, GDM-23-HST02-HC, TGO-27-POP01, GDM-23-HST02-HC
hrSHours of the real time clockTGO-27-POP01, TGO-27-POP01, GDM-23-HST02-HC
hrSReal time clock hoursGDM-23-HST02-HC
hrSDisplays the real time clock hour.GDM-49-SCI-HC
hrSHours shown by the real-time clock.GDM-49-SCI-HC
hStHealth Safety Timer password entryTGO-27-POP01, GDM-23-HST02-HC, TGO-27-POP01, GDM-23-HST02-HC
hSt/dLYDelays checking Health Safety Timer conditionsTGO-27-POP01, GDM-23-HST02-HC
hSt/dLYDelays Health Safety Timer condition checksGDM-23-HST02-HC
hSt/dLYDelay for checking Health Safety Timer conditionsTGO-27-POP01
hSt/tStTests the Health Safety LockTGO-27-POP01, GDM-23-HST02-HC
hSt/tStHealth Safety Lock testingGDM-23-HST02-HC
hSt/tStTesting the Health Safety LockTGO-27-POP01
H₂OSump tank did not fill within three minutes.Check the water filter, incoming pressure, inlet valve, and drain valve.TCIM-422-FA1-A~*-#
LAMinimum temperature alarm.TRM2L******#*******#, Commercial Refrigerator
LoAppliance low temperature alarmTGO-27-POP01, GDM-23-HST02-HC, TGO-27-POP01, GDM-23-HST02-HC
LoThe cabinet temperature is too low.GDM-49-SCI-HC
LoLow temperature≤ 36 °F (2 °C) for ≥ 5 minCommercial Refrigerator
LoCabinet low temperature alarm.GDM-49-SCI-HC
LocKeypad is lockedPress the down arrow until the display shows Loc.TGO-27-POP01, GDM-23-HST02-HC, TGO-27-POP01, GDM-23-HST02-HC
LocThe keypad is locked.GDM-49-SCI-HC
minMinute of the real time clockTGO-27-POP01, TGO-27-POP01, GDM-23-HST02-HC
minReal time clock minuteGDM-23-HST02-HC
minDisplays the real time clock minute.GDM-49-SCI-HC
minMinute shown by the real-time clock.GDM-49-SCI-HC
oFFController is in standby.Hold the power button until the display shows OFF.TRM2L******#*******#, Commercial Refrigerator, TGO-27-POP01, GDM-23-HST02-HC
oFFThe controller is in standby mode.GDM-49-SCI-HC
onControl is turned onPress and hold Cancel until on appears.TGO-27-POP01
P1Thermostat probe failure.TRM2L******#*******#, Commercial Refrigerator
P2Evaporator probe failure.TRM2L******#*******#, Commercial Refrigerator
P3Auxiliary probe failure.TRM2L******#*******#, Commercial Refrigerator
PFPower failureTGO-27-POP01, GDM-23-HST02-HC, TGO-27-POP01, GDM-23-HST02-HC
PoFControl is locked.Hold both arrow buttons until the display shows PoF.TRM2L******#*******#, Commercial Refrigerator
PonControl is unlocked.Hold both arrow buttons until the display shows Pon.TRM2L******#*******#, Commercial Refrigerator
SttStart time for timed actionsTGO-27-POP01, TGO-27-POP01, GDM-23-HST02-HC
SttStart time for scheduled actionsGDM-23-HST02-HC
t1Current probe 1 temperatureTGO-27-POP01
t1Current temperature from probe 1GDM-23-HST02-HC
t1Shows the current temperature from probe 1.GDM-49-SCI-HC
t1Instant temperature from probe 1TGO-27-POP01, GDM-23-HST02-HC
t1Instant temperature of probe 1.Press info to show t1.GDM-49-SCI-HC
t2Current probe 2 temperatureTGO-27-POP01
t2Current temperature from probe 2GDM-23-HST02-HC
t2Shows the current temperature from probe 2.GDM-49-SCI-HC
t2Instant temperature from probe 2TGO-27-POP01, GDM-23-HST02-HC
t2Instant temperature of probe 2.GDM-49-SCI-HC
t3Current probe 3 temperatureTGO-27-POP01
t3Current temperature from probe 3GDM-23-HST02-HC
t3Shows the current temperature from probe 3.GDM-49-SCI-HC
t3Instant temperature from probe 3TGO-27-POP01, GDM-23-HST02-HC
t3Instant temperature of probe 3.GDM-49-SCI-HC
thiMaximum recorded probe 3 temperatureTGO-27-POP01, TGO-27-POP01
thiHighest recorded probe 3 temperatureGDM-23-HST02-HC
thiDisplays the highest recorded temperature from probe 1.GDM-49-SCI-HC
thiMaximum recorded temperature from probe 3GDM-23-HST02-HC
thiMaximum recorded temperature of probe 1.GDM-49-SCI-HC
tLoMinimum recorded probe 3 temperatureTGO-27-POP01, TGO-27-POP01
tLoLowest recorded probe 3 temperatureGDM-23-HST02-HC
tLoDisplays the lowest recorded temperature from probe 1.GDM-49-SCI-HC
tLoMinimum recorded temperature from probe 3GDM-23-HST02-HC
tLoMinimum recorded temperature of probe 1.GDM-49-SCI-HC